DXi9000 Series Environmental Specifications

Temperature |
Operating |
10° to 35°C (50° to 95°F) with a maximum temperature gradient of 10C (18F) per hour. Note: 35C is the maximum temperature for the DXi9000 at 950m (3,117ft). Reduce the maximum temperature by 1C/300m (1F/547ft) above 950m (3,117 ft). |
Shipping |
–40°C to 60°C (–40°F to 140°F) with a maximum temperature gradation of 20C (36F) per hour. |
|
Storage | -10 to 50C (-14 to 122F) with a maximum temperature gradation of 15C (27F) per hour | |
Relative Humidity1 |
Operating |
20% to 80% (non-condensing) with 26C (79F) maximum dew point with a maximum gradient of 10% per hour. |
Shipping |
5% to 90% (non-condensing) with 33C (91F) maximum dew point. with a maximum gradient of 10% per hour. |
|
Storage | 10% to 90% (non-condensing) with 33C (91F) maximum dew point. with a maximum gradient of 10% per hour | |
Altitude |
Operating and Storage |
– 16m to 3048m (– 50 to 10,000 ft) |
Shipping |
-16 to 12,000m (-50 to 39,370ft) |
|
1Atmosphere must be non-condensing at all times. |

Sine Vibration |
Operating |
Random 0.26 G’s, 5–350 Hz (all operation orientations). |
Non-operating |
Random 1.88 G’s, 10-500 Hz for 15 minutes (all six sides tested). |
|
Shock Vibration |
Operating |
6 G’s for 11 ms, half-sine input, 6 shock pulses in both + and – directions operational axis |
Non-operating |
71 G’s for 2 ms, half-sine input, 6 shock pulses in both + and – directions operational axis |

Acoustic output |
Operating |
Sound Pressure Level 72 dbA maximum at any operation position |

EMC/Safety |
47 CFR part 15 Class A CNS 13438 Class A CISPR 22 Class A CISPR 24 Class A EN 55022 Class A EN 55024 EN 60590-1 EN 61000-3-2 EN 61000-3-3 IEC 60950-1 ICES-003 Class A VCCI V-3/2000 Class A AS/NZS 3548 Class A KN22 Class A KN24 UL 60590-1 |
|
Immunity Tests
Standards: EN55024: 1998 +A1: 2001 +A2:2003 KN24 |
IEC 61000-4-2 (Ed. 2.0 2008-12) - Electrostatic Discharge (ESD) IEC 61000-4-3 (Ed. 3.1 2008-04) - Radiated RF Immunity IEC 61000-4-4 (Ed. 2.0 2004-07) - Electrical Fast Transient/Burst IEC 61000-4-5 (Ed. 2.0 2005-11) - Surge Immunity IEC 61000-4-6 (Ed. 2.2 2006-05) - Conducted RF Immunity IEC 61000-4-8 (Ed. 1.1 2001-03) - Magnetic Field IEC 61000-4-11 (Ed. 2.0 2004-03) - AC Dips and Interrupts |
Caution: The DXi9000 Series system is designed to be installed in a rack enclosure. Ensure that the operating temperature inside the rack enclosure does not exceed the maximum rated ambient temperature. Do not restrict air flow to the DXi components.