Remove and Replace the SCB

Overview

The System Control Blade (SCB) is the main controller for all library operations. It contains the user interface operations, Web Services, and it stores the configuration.

The SCB is located in the Control Module (CM).

Item Name Description

1

Power Switch The power switch initiates the shutdown procedure when you press it for two seconds. If you press it for five seconds, you will force a hard shutdown. It is solid green and illuminated when the library is powered on.
2 Status LEDs

Normal indications:

  • Green: Blinks once per second
  • Amber: Off
  • Blue: Blinks once every 10 seconds
3 Serial Port The serial port is for engineering use only.
4 Service Port The service port allows you to connect directly to the library to perform service functions.
5 Service USB The service USB port is not used at this time.
6 Ethernet Ports

The Ethernet ports allow you to connect the library to a network. This allows you to connect to hosts and to configure and operate the library through the WebGUI. While the ports are identical in function, use Gb1 as your primary network connection and Gb2 as your secondary connection. There are two for redundancy.

GB1 and GB2 correspond to the interface settings in the Scalar i3 Network Settings menu.

Before You Begin

Before you begin the removal procedure, take a snapshot of the library and save your library configuration.

Important Information: SCB and Control Module Replacements

If the existing SCB is being moved from an existing Control Module (CM) to a replacement CM, it must have a Reset to Factory Default performed on it to clear the old configuration on the existing CM.

The Factory Defaults feature will revert your library back to its initial configuration. This means that any partitions created, or users setup or slot allocation as well as many other features will be lost.

The only library configuration data that will be retained is IP address settings. You should only use this feature when approved of, or requested by, Quantum Service. Before resetting the library to its factory defaults, always save your configuration for possible restoration.

  1. From the WebGUI Navigation panel, select Service.
  2. In the Operations panel, click Factory Defaults.

If you save the library configuration before removing the SCB, you can only restore it on an SCB that is going into the exact same CM. If you replace the CM and perform a Reset to Factory Default, you cannot restore the library configuration.

Remove the SCB

WARNING: Do not move SCBs from one library to another another library. If you must replace the SCB in a library, contact Quantum and request a new SCB.

Replace the SCB

WARNING: Do not move SCBs from one library to another another library. If you must replace the SCB in the library, contact Quantum and request a SCB CRU.